/ Perfect Charging / Perfect Welding / Solar Energy42,0426,0204,EN 001-01042015Fronius Primo:Explanation of symbols and choice of location Notes regar
8If the inverter is installed in a switch cabinet or a similar sealed area, then forced-air ven-tilation must be provided to ensure adequate heat diss
9ENInstallation notesSelecting wall plugs and screwsRecommended screwsTo install the inverter, the manufacturer recommends the use of steel or alumini
10Notes regarding grid connectionMonitoring the GridAC terminalsPE Ground conductor / groundingL1 Phase conductorN Neutral conductorMax. cross-section
11ENConnecting alu-minum cablesThe AC-side terminals are designed for connecting single-wire, round, aluminum cables. The following points must be tak
12If AC cables are laid over the shaft of the DC main switch or across the connection block of the DC main switch, they may be damaged when the invert
13ENMaximum fuse rating on alternat-ing current sideAC ~max. 63 AInverter Phases Max. output Max. fuse ratingFronius Primo 3.0-1 1 3000 W 1 x C 63 AFr
14Notes regarding DC connectionGeneral com-ments regarding solar modulesTo enable suitable solar modules to be chosen and to use the inverter as effic
15ENConnecting alu-minum cablesThe DC-side terminals are designed for connecting single-wire, round aluminum cables. The following points must be take
16Inverter DC con-nectionThe inverter is designed to be connected and used exclusively in conjunction with ungrounded solar modules. The solar modules
17ENInverter with mul-tiple MPP track-ersIn the case of inverters with multiple MPP trackers, there are two independent DC inputs (MPP trackers) avail
18Single MPP tracker mode with only one string on an inverter with multiple MPP trackers:Connecting only one string to an inverter with multiple MPP t
19ENNotes regarding the laying of data communication cablesLaying data com-munication ca-blesIMPORTANT! Operating the inverter with an option card and
20Notes regarding attaching the inverter to the wall bracketAttaching the in-verter to the wall bracketThe side sections of the housing lid are design
21ENNotes regarding software updatesNotes regarding software updatesIf the inverter is supplied with a USB stick, the inverter software must be update
22USB Stick as a Data Logger and for Updating Invert-er SoftwareUSB stick as a data loggerA USB stick connected to the USB A socket can act as a data
23EN(1) ID(2) Inverter no.(3) Inverter type (DATCOM code)(4) Logging interval in seconds(5) Energy in watts per second, relative to the logging interv
24When the buffer memory is full, the oldest data in the memory will be overwritten by the next batch of data.IMPORTANT! The buffer memory requires a
25ENRemove USB stickSecurity note concerning the removal of a USB stick:IMPORTANT! To avoid any loss of data, a USB stick may only be removed if the f
26Notes regarding maintenanceMaintenanceCleaning Clean the inverter and the display as required with a damp cloth.Do not use cleaning agents, abrasive
27EN
1ENContentsExplanation of symbols ...
Fronius Worldwide - www.fronius.com/addressesUnder http://www.fronius.com/addresses you will find all addresses of our sales branches and partner firm
3ENExplanation of symbolsExplanation of safety symbolsIf you see any of the symbols depicted in the "Safety rules" chapter, special care is
4Can be used at altitudes of up to 4000 mIMPORTANT! The inverter must not be installed or used at altitudes above 4000 m. Do not install the inverter:
5ENExplanation of symbols - instal-lation positionThe inverter is designed to be installed vertically on a vertical wall or pil-lar.The inverter is su
6Do not install the inverter such that it overhangs with its connection sock-ets facing downwards.Do not install the inverter on the ceiling.
7ENChoice of locationProper use The inverter is designed to be connected and used exclusively in conjunction with un-grounded solar modules. The solar